Plenum cable /ˈplɛnəm/ is electrical cable that is laid in the plenum spaces of buildings. In the United States, plastics used in the construction of plenum cable are regulated under the National Fire Protection Association standard NFPA 90A: Standard for the Installation of Air Conditioning and Ventilating Systems. All materials intended for use on wire and cables to be placed in plenum spaces are designed to meet rigorous fire safety test standards in accordance with NFPA 262 and outlined in NFPA 90A.

Plenum cable is required because, if nonplenum cable catches fire, it can release toxic fumes. If those fumes are released in a plenum space, they can spread throughout the building through the air circulation system.[1]

Plenum cable is jacketed with a fire-retardant plastic jacket of either a low-smoke polyvinyl chloride (PVC) or a fluorinated ethylene polymer (FEP). Polyolefin formulations, specifically based on polyethylene compounding had been developed by at least two companies in the early to mid-1990s; however, these were never commercialized, and development efforts continue in these yet-untapped product potentials. Development efforts on a non-halogen plenum compound were announced in 2007 citing new flame-retardant synergist packages that may provide an answer for a yet-underdeveloped plenum cable market outside the United States.

In 2006, significant concern developed over the potential toxicity of FEP and related fluorochemicals including the process aid perfluorooctanoic acid (PFOA) or C8 such that California has proposed some of these materials as potential human carcinogens. The NFPA Technical Committee on Air Conditioning, in response to public comment, has referred the issue of toxicity of cabling materials to the NFPA Committee on Toxicity for review before 2008.

In 2007, a development program specifically targeting the production of a non-halogen plenum cable compound was announced to specifically address lingering toxicity concerns presented by halogenated compounds for use in European and other global markets.

Riser cable

edit

Cable that is run between floors in non-plenum areas is rated as riser cable.[2] The fire requirements on riser cable are not as strict. Thus, plenum cable can always replace riser cable, but riser cable cannot replace plenum cable in plenum spaces.

Both plenum and riser cables commonly include a rope or polymer filament with high tensile strength, which helps support the weight of the cable when it is dangling in an open chute.

Cables like twisted-pair, coaxial, HDMI, and DVI are available in both plenum and riser versions. The cable cost is often significantly higher than general-use cable due to the special restricted-use flame retardant materials.

Cable stiffness

edit

Plenum-rated and riser-rated cables are restricted to only allow certain chemicals for manufacture of the wire insulation and cable sheath. Typically this results in reduced flexibility of plastic cables, making it stiff and hard to bend. The bend radius may also be increased, and tight bends can potentially crack or tear the insulation and sheathing.

References

edit
  1. ^ Hallberg, Bruce A. (2014). Networking: A Beginner's Guide (Sixth ed.). New York. p. 51. ISBN 9780071812245.{{cite book}}: CS1 maint: location missing publisher (link)
  2. ^ "Intrabuilding riser cable-- a look at the basics". www.cablinginstall.com. March 1997. Retrieved 2017-12-15.
edit

The videos here, while presenting a comparative viewpoint, do not show the fire tests used to determine the relative acceptability of cables for use in plenum spaces. The fire tests shown in the referenced link are small scale (bench) demonstrations of relative burning characteristics under one condition that is not sanctioned by or used by any safety code or regulation in determining suitability for use in plenum or other applications.

📚 Artikel Terkait di Wikipedia

Structured cabling

telecommunications, Structured cabling is the design and installation of a complete, standards-compliant telecommunications cabling infrastructure for building

Plenum

Look up plenum in Wiktionary, the free dictionary. Plenum may refer to: Plenum chamber, a chamber intended to contain air, gas, or liquid at positive pressure

Category 5 cable

"Horizontal Cabling". The Network Encyclopedia. Retrieved 2013-05-12. "ANSI/TIA/EIA-568-B.2-2001, Commercial Building Telecommunications Cabling Standard"

Coaxial cable

carry the tension involved in an aerial drop from a utility pole. "Plenum" cabling is expensive and comes with a special Teflon-based outer jacket designed

Plenum space

A plenum space is a part of a building that can facilitate air circulation for heating and air conditioning systems, by providing pathways for either heated/conditioned

Cable tie

detectors. Cable ties made of ETFE (Tefzel) are used in radiation-rich environments. Red cable ties made of ECTFE (Halar) are used for plenum cabling. Stainless

Fiber-optic cable

twist to allow for stretching. Domestic outdoor FTTP cable A critical concern in outdoor cabling is to protect the fiber from damage by water. This is

Dropped ceiling

flame spread inside the unseen plenum space, in the event of high voltage equipment or wiring failure. Low-voltage cabling is permitted because current