Insulation monitoring device
Insulation monitoring device

An insulation monitoring device monitors the ungrounded system between an active phase conductor and earth. It is intended to give an alert (light and sound) or disconnect the power supply when the resistance between the two conductors drops below a set value, usually 50 kΩ (sample of IEC standard for medical applications). The main advantage is that the ungrounded or floating system allows a continuous operation of important consumers such as medical, chemical, military, etc.

Some manufacturers of monitors for these systems are capable of handling VFDs (Variable Frequency (Speed) Drives). Most, however are not due to issues with the DC-portions of the VFDs.

Most monitors work by injecting low level DC on the line and detecting. Some manufacturers use a patented AMP-monitoring principle (Adapted Measuring Pulse)[citation needed]

Insulation Monitoring Devices (IMD) according to IEC 61557-8

edit

This part of IEC 61557 specifies requirements for insulation monitoring devices (IMD), which permanently monitor the insulation resistance RF to earth of unearthed a.c. IT systems, of a.c. IT systems with galvanically connected d.c. circuits having nominal voltages up to 1 000 V a.c., as well as of unearthed d.c. IT systems with voltages up to 1 500 V d.c. independent from the method of measuring.[1]

According to 61557-8: Insulation monitoring devices must be able to monitor both symmetrical and asymmetrical insulation faults according to their specified measuring principle. A symmetrical fault in insulation occurs when the insulation resistance of all conductors in the network to be monitored is (approximately) evenly reduced. An unsymmetrical fault in insulation occurs when the insulation resistance, e.g. of one conductor is reduced much more than that of the remaining conductor(s). Relays, which use the unbalance voltage (3 voltmeter method), are not insulation monitoring devices according to this standard. Under special network conditions, a combination of several measurement methods may be necessary to fulfill the monitoring task, including an asymmetry monitoring.[2]

Terminology

edit

Terminology differs by region and by market segment.

  • For the system type different terms are used: "IT system" (lat. Isolation Terra) vs. "floating system" vs. "ungrounded system".[3]
  • For the monitoring device different terms are used: "Insulation monitoring device" vs. "ground fault relay" vs. "ground fault detector" vs. "LIM" (Line Isolation Monitor)

Standards

edit
  • IEC 61557-8:2014, "Electrical safety in low voltage distribution systems up to 1 000 V a.c. and 1 500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 8: Insulation monitoring devices for IT systems"
  • IEC 61557-9:2014, "Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. - Equipment for testing, measuring or monitoring of protective measures - Part 9: Equipment for insulation fault location in IT systems"

Literature

edit
  • Wolfgang Hofheinz: Protective Measures with Insulation Monitoring VDE Application of Unearthed IT Power Systems in Industry, Mining, Railways, Marine/ Oil and Electric/Rail Vehicles, ISBN 978-3-8007-2958-6, E-Book: ISBN 978-3-8007-4106-9

Further reading

edit

References

edit
  1. ^ "IEC 61557-8". IECEE. 2020-12-20.
  2. ^ "Insulation monitoring: The concept". Bender GmbH & Co. KG. 2020-12-20.
  3. ^ "Application and Operation of Insulation Monitors in Unearthed (floating-IT) Rail Signal Power Systems". IEEE Xplore. January 2007. pp. 167–184. Retrieved 2020-12-20.

📚 Artikel Terkait di Wikipedia

Residual-current device

and sockets Arc-fault circuit interrupter Electrical injury Insulation monitoring device Isolation transformer Protective relay RCD and RCCB are international

Insulator (electricity)

and portable power tools. Double insulation requires that the devices have both basic and supplementary insulation, each of which is sufficient to prevent

Earthing system

a small number of loads each and should be protected with an insulation monitoring device (generally used only by medical, railway or military IT systems

Circuit breaker

Ground Fault Circuit Interrupter (GFCI) Hybrid switchgear module Insulation monitoring device Motor control center (MCC) Network protector Power distribution

Electrical fault

fault and continue in operation. Wiring codes may require an insulation monitoring device to give an alarm in such a case, so the cause of the ground fault

IMD

variant by Silicon Graphics), in versions 5.1–6.4 Insulation monitoring device, a protection device or circuit in electric systems Intermodulation distortion

Dielectric withstand test

test, or insulation test) is an electrical safety test performed on a component or product to determine the effectiveness of its insulation. The test

Qualitrol

condition monitoring technology company headquartered in Fairport, New York. Qualitrol manufacturers and distributes partial discharge monitoring, asset